Overview
4-Quadrant Regenerative AC Drive
drive.web distributed Control
Near Unity Power Factor & Full Torque from zero speed
Ultra-low harmonics
UL & STO (Pending)
IP20 Packaging
- 10 TO 30 HP -
Artificial lifts
Converting Lines
Energy generation / transfer & recovery
Extrusion & Molding
Flywheels
Low harmonic or regen fans
Low harmonic or regen pumps
Material handling equipment
Packaging
Printing & Coating
Process control
Pumped hydro
Textiles
Wind turbines
Winding / Unwinding
High performance AC vector drives for coordinated drive systems and precision machine control.
Features
- Open-loop V/f and closed-loop vector control for induction motors
- Constant and quadratic torque modes with current loop autotune
- High-precision closed-loop speed accuracy (0.02%)
- Four-quadrant regenerative operation
- 380–500Vac, three-phase, 50/60Hz input
- Output frequency up to 200Hz
- Full featured programmable control
- Graphical Function Block programming
- drive.web distributed control
- Built-in PID, advanced math, winder, motion and position control
- Comprehensive diagnostics and monitoring
- Motor current, voltage, speed and power
- AC supply voltage and frequency
- Heatsink and motor temperature (PT100 input)
- Run and powered hours
- Integrated communications
- drive.web smart Ethernet
- Modbus TCP/IP and Ethernet/IP
- USB-C
- Optional PROFIBUS, PROFINET, DeviceNet, EtherCAT, Modbus and CAN/CANopen
- Flexible I/O configuration with analog and digital inputs/outputs
- Dual incremental encoder support (5V / 12V / 24V selectable)
- Comprehensive protection including thermal, over-current, stall and power loss protection
- IP20 enclosure, air-cooled with temperature-controlled fans
- 0–50°C operating temperature (derate above 40°C)
- Integrated operator station with 2 × 20 character backlit LCD, local/remote control and dedicated Run/Jog/Stop keys
- CE compliant; UL pending; STO Pending
dw4Q - Smart AC Drive
The drive.web automation technology uses distributed control over Ethernet to provide cost effective systems integration for systems of any size or complexity.
Specifications
Input Ratings
| Supply Voltage | 380 – 500Vac, Three-Phase |
| Supply Frequency | 50 / 60 Hz |
| Regeneration | Four-Quadrant Regenerative |
| Auxiliary Supply | Optional 24VDC Input |
| EMC Filter | Internal (Standard) |
Output Ratings
| Power Rating | 10, 15, 20, 25, 30 HP (7.5, 11, 15, 18.5, 22 kW) |
| Current Rating – Normal Duty | 18, 26, 35, 44, 52A — 110% overload for 30 seconds |
| Current Rating – Heavy Duty | 15, 22, 30, 37, 44A — 150% overload for 30 seconds |
| Output Voltage | Vout ≤ 0.86 × Vin |
| Maximum Output Frequency | 200 Hz |
| Speed Accuracy | 2% (Open-Loop V/f) 0.02% (Closed-Loop Vector) |
Control
| Motor Compatibility | Induction Motors |
| Control Modes | Open-Loop V/f Closed-Loop Vector |
| Torque Modes | Open-Loop Constant Torque Open-Loop Quadratic Torque |
| Speed Control | Yes |
| Autotune | Current Loop Autotune |
Application Functions
| Programmable Control | Full Featured |
| Functions Included | Analog Logic PID Controllers Advanced Math Winder Control Motion Control Position Control |
Diagnostics
| Motor Monitoring | Current Voltage Speed Power |
| AC Supply Monitoring | Voltage Frequency |
| Temperature Monitoring | Heatsink Temperature Motor Temperature (External Sensor Required) |
| Input Monitoring | User Input Voltages |
| Runtime Monitoring | Run Hours Powered Hours |
Communications
| Standard Interfaces | drive.web Smart Ethernet Modbus TCP/IP Ethernet/IP USB-C |
| Optional Networks | PROFIBUS PROFINET DeviceNet EtherCAT Modbus CAN / CANopen All Major Industrial Networks |
| Programming | Graphical Function Block Programming drive.web Distributed Control |
I/O Specification
| Analog Inputs | 3 × ±10V configurable reference supplies (10mA max) 1 × 4–20mA or ±10V configurable reference |
| Analog Outputs | 2 × configurable, ±10V range |
| Digital Inputs | 24V logic, current sinking 4 dedicated: Run, Stop, Jog, Coast Stop Additional configurable inputs |
| Digital Outputs | 24V logic, current sourcing (400mA max) 5 configurable |
| Relay Outputs | 2 configurable, 240VAC volt-free contacts |
| Encoder Inputs | Single or Dual Incremental A, B, Marker Differential or Single-Ended 5V / 12V / 24V (Software Selectable) |
| Motor Temperature Input | 1 × PT100 (External Sensor Required) |
Protection
| Protection Features | Thermal Fold-Back Instantaneous Over-Current Motor Over-Temperature Heatsink Over-Temperature AC Power Loss AC Line Sync Loss Stall Protection Standstill Logic Fan Fail Digital/Analog Output Short-Circuit Digital/Analog Input Over-Voltage (to 30VDC) |
Environmental
| Operating Temperature | 0 – 50°C (Derate above 40°C) |
| Storage Temperature | -25°C to +55°C |
Enclosure
| Ingress Protection | IP20 |
| Cooling | Air-Cooled with Temperature-Controlled Fans |
| Mounting | Keyhole Slot Mounting |
| Control Connections | Two-Part Control Connections |
Standards
| Compliance | EN 61800-5-1:2007 (CE – Low Voltage Directive) EN 61800-3:2017 (CE – EMC) EN 61800-5-2:2017 (STO Pending) UL 61800-5-1 (UL Pending) |
Dimensions
| Frame Size | 1 | 2 |
| Protection | IP20 | IP20 |
| Height | 22.7” (576 mm) | 22.8” (578 mm) |
| Width | 10.4” (264 mm) | 10.4” (264 mm) |
| Depth | 9.2” (234 mm) | 11.4” (289 mm) |
| Weight | 48.5 lbs (22 kg) | 55.1 lbs (25 kg) |
Downloads
To download P2 Series manuals, drawings, and more, please make a selection from the dropdown menu below:
Brochures
| Filename / Link | Size |
|---|---|
| bardac-generis-brochure-1.3-web.pdf | 5.35 Mb |
Flyers
| Filename / Link | Size |
|---|---|
| Generis 5x7 sign-v3.1.pdf | 1.05 Mb |